|
1. APPROVAL OF SERVICE CONNECTIONS
The
Division of Water reserves the right to approve or change
proposed service connection plans, pipe sizes and meter sizes
according to the Division's requirements.
2. SERVICE TAPS BY THE DIVISION OF WATER
All
service taps are to be performed by the Division of Water or a
contractor authorized by the Commissioner of CWD.
3. DOMESTIC SUPPLY FOR MORE THAN ONE BUILDING
A domestic
service line shall supply no more than one building.
4. DEPTH OF SERVICE PIPE
Depth of
service pipe from the water main to the curb valve/meter vault
for domestic and fire service shall not be less than 6 feet from
the established grade and from curb valve/meter vault to
building shall not be less than 5 ½ feet from established grade.
5. SERVICE PIPE MATERIAL TWO INCH AND LESS
All service pipe from the curb valve to the home or
building with a nominal diameter of two inch and less for
domestic purposes shall be Type K Copper for all connections 150
feet and less as measured from the right-of-way to the face of
home or building.
High-density polyethylene (HDPE) SDR 9, manufactured for potable water application
may be used in lieu of copper under the following conditions:
-
The service connection is in excess of 150 feet
as measured from the right-of-way to the face of home or
building.
-
The meter is to be placed
in a vault in the right of way or in an easement contiguous
to the right-of-way.
-
A double-check backflow
prevention device must be installed in the vault immediately
downstream of the meter.
-
The backflow prevention
device is to be tested annually and a test and maintenance
form must be submitted at the time of each annual test by a
certified backflow prevention device tester.
For all the test and tester requirements see the
“backflow” section of our website at
http://www.clevelandwater.com/system_overview/operations_backflow06.
-
The piping from the main to
the meter and within the meter vault shall be Type K
Copper. HDPE may be used from the outlet of the meter
assembly to the house or building.
-
HDPE pipe must meet all applicable performance
standards for a pressure rated applications as required in
NSF/ANSI Standard 14, and shall comply with NSF/ANSI
Standard 61 for health effects. HDPE pipe must be marked as
NSF-pw (NSF compliant for potable water)
-
The
HDPE Pipe must meet all requirements of
AWWA C901, AWWA C906, NSF 14, NSF 61 and ASTM D3035. Where
intermediate joints are necessary connections must be made
by either the use of a compression coupling with insert
rings or by creating a fusion butt weld.
All material between the curb valve and the house or
building is the responsibility of the property owner.
Where HDPE Pipe is used, the Division of Water recommends that
the owner install a tracer tape system so that their connection
can be located in the future and that our 5 1/2' depth
requirements are strictly adhered to so that the line is not
susceptible to freezing as HDPE can not be thawed by the
Division of Water.
Type K Copper must be used between the water main
and the curb valves in all applications. HDPE will only be
considered upon a written
request by the applicant to the Division of Water
Type K Copper must be used in all fire service
applications with no exceptions.
All service line materials and installation procedures
must also meet local building and fire code criteria where
applicable.
6. SERVICE PIPE MATERIAL GREATER THAN TWO-INCHES
All service pipe from the
curb valve to the home or building with a nominal diameter
greater than two inch shall be Class 52 Cement Lined Ductile
Iron Pipe for all connections 150 feet and less as measured from
the right-of-way to the face of home or building.
PVC Pressure Rated Pipe SDR 18 or thicker as per
ASTM D2241 manufactured
for potable
water application may be used in lieu of
Class 52 Cement Lined
Ductile Iron Pipe
for connections in
excess of 150 feet
as measured from the right-of-way to the face of
home or building. Domestic Service lines in excess of 150
feet also require a meter vault. In such instances, all
the piping from the main to the meter and within the meter vault
shall be Class 52 Cement Lined Ductile Iron Pipe. PVC may
be used from the outlet of the meter assembly to the house or
building.
The PVC pipe shall be manufactured and tested in
accordance with AWWA Standard C900 for “Polyvinyl Chloride (PVC)
Pressure Pipe and Fabricated Fittings, 4 in. through 12 in. (100
mm through 300 mm), for Water Distribution”, or AWWA Standard
C909 for “Molecularly Oriented Polyvinyl Chloride (PVCO)
Pressure Pipe, 4 in. through 12 in. (100 mm through 300 mm), for
Water Distribution” and clearly marked as such. PVC water
pipe shall be certified to NSF International Standard No. 61.
All material between the curb valve and the house or
building is the responsibility of the property owner.
Where PVC Pipe is used, the Division of Water recommends that
the owner install a tracer tape system so that their connection
can be located in the future and that our 5 1/2' depth
requirements are strictly adhered to so that the line is not
susceptible to freezing as PVC can not be thawed by the Division
of Water.
-
Class 52 Cement Lined Ductile Iron Pipe must
be used between the water main and the curb valves with no
exceptions. All 3” service lines must be Class
52 Cement Lined Ductile Iron Pipe in their entirety from the
main to the house or building regardless of setback
distance.
-
Class 52 Cement Lined Ductile Iron Pipe must
be used in all fire service applications with no exceptions.
-
All service line materials and installation
procedures must also meet local building and fire code
criteria where applicable.
7. SERVICE PIPE IN SEWER TRENCHES
Service
pipes shall not be laid in sewer trenches except in rock
excavation, in which case the service pipe may be put on a shelf
not less than eight-inches wide, cut into the side of the
trench. In all other cases, there shall not be less than 5 feet
between centers of service pipes and sewer pipes.
8. SIZE OF
WATER MAINS THAT CANNOT BE TAPPED FOR SERVICE CONNECTIONS
Water
mains sixteen-inches and larger shall not be tapped for service
connections.
9. MINIMUM SIZE OF SERVICE TAP
Taps less
than one-inch in diameter shall not be approved.
10. BENDS ON SERVICE PIPE
No
horizontal bends are permitted on the service pipe prior to
(upstream) of the curb valves.
11. LOCATION OF CURB VALVES
All
service connections require curb valves that shall be located in
the right of way approximately three feet behind the face of
curb. For water mains in easements, curb valves shall be located
approximately three feet from the water main unless otherwise
directed by CWD. If
no curb exists, criteria shall be established from edge of
pavement.
12. MORE THAN ONE DOMESTIC SERVICE LINE TO A SINGLE BUILDING
If more
than one domestic service line is used to supply one building
then the Division of Water reserves the right to make a
determination with regard to allowing this arrangement.
13. FIRE SUPPLY FOR MORE THAN
ONE BUILDING ON
A SINGLE PARCEL
A fire
service line shall supply no more than one building. If the
local fire department requires looping of the fire line then the
Division of Water will evaluate these situations case by case.
14. SERVICE LINES CROSSING PROPERTY LINES
Under no
circumstances shall a service line cross property lines unless
one parcel is landlocked and therefore has no frontage to the
water main. In cases such as these, a copy of the
agreement/easement between the two property owners must be sent
to the Permits and Sales Department.
15. SERVICE CONNECTIONS ALONG FRONTAGE OF PROPERTY
A service
connection to a water main shall be permitted only if the water
main extends across the full frontage of the premises.
16. SERVICE
CONNECTIONS TO CORNER LOTS OR LOTS THAT ABUT TWO STREETS
A service
connection to a lot that abuts more than one street will be
permitted only if the lot has a water main that is extended
across the full frontage as well as across the property limits
on the side street(s) in which the property abuts.
17. LOCATION OF TAP NOT ALONG FRONTAGE OF PROPERTY
A service
tap can be made on any street that abuts the property limits as
long as water mains are extended across the street(s) in which
the property abuts as stated in Policy #2.
18. PLUGGING EXISTING SERVICE CONNECTIONS
When a new
service connection permit is issued, all existing service
connections to the property must be plugged at the water main
and is the responsibility of the owner.
19. CASING FOR SERVICE CONNECTIONS
No casing
is permitted on service connections before the curb valve(s)
unless the service line is going under a utility greater than
24-inches in diameter. Steel casings are the only casings
permissible. This policy excludes PVC casing for new subdivision
connections.
20. SINGLE FEED-DUAL SERVICE CONNECTIONS
A domestic
service connection that comes off the fire service connection
must be teed off in the right-of-way before either service line
enters the meter or the backflow vault. The fire service line is
not permitted to tee off the domestic service line.
21. REUSING EXISTING SERVICE CONNECTIONS
An
existing service connection can be reused only if the new
service pipe after the curb valve is of the same nominal
diameter as the existing connection.
22. NO CONNECTIONS OFF CIRCULATION MAINS
No service
connection can be tapped off a designated circulation main.
A circulation main is defined as a mains installed for
the purpose of providing circulation and installed in an
easement.
23. Connecting different service
districts
Unless special permission is given by the Commissioner of
Water, no arrangement of pipes connecting different service
districts will be permitted.
24. DISTANCE BETWEEN TAPS
One-inch connections shall have a minimum distance of five
feet between taps when the taps are made on the same side of the
water main. One-inch connections made on opposite sides of the
water main require a minimum distance of 18-inches. Connections
larger than one-inch require a minimum distance of five feet
between taps. A minimum distance of five feet is required
between the tap and a hydrant tee or valves. A minimum distance
of 2 feet is required between a tap and the bell or a bend.
25. THREE TIERED CAMPUS MODEL ON A SINGLE PARCEL
When three
or more buildings are situated on a single parcel and the
buildings are arranged in such a manner as being placed one
behind the other (three tiered), the Division of Water will
review these on a case by case basis.
26. BYPASS ON METER SETTERS
Bypass
lines are not permitted on meter setters inside buildings.
27. LOCATION OF METER VAULTS
Meter
vaults are to be installed in the right-of-way or within the
water main easement or adjacent to either the right-of-way or
water main easement in a meter vault easement.
28. ONE METER ALLOWED
PER SERVICE CONNECTION
Only one
meter shall be set on one service line unless the owner is
installing a deduct meter for irrigation purposes. The deduct
meter is to be purchased from the Division of Water or from an
approved manufacturer, in which case, the meter must be sent to
the Division's meter shop to be calibrated. The Division reads
both the domestic meter and the deduct meter but is not
responsible for repairs to the deduct meter. The local sewer
authority has jurisdiction over granting a separate service for
irrigation only.
29. SUB METERING
The
Division of Water will not sub meter any property.
30. PLACEMENT OF METER
A meter vault is required when the size of the meter is
3-inches and greater unless special permission is granted by the
Commissioner of Water. A meter vault will also be required if
the distance between the existing right-of-way and the domestic
service point of entry into the building is more than 150 feet.
The meter must be installed immediately after entering the
building in a horizontal position a maximum of 36-inches from
the basement floor. The backflow device for a commercial
connection is to be installed immediately after the meter.
31. BACKFLOW PREVENTION DEVICES
The Division of Water requires backflow prevention devices
on all commercial service connections.
The Division of Water also requires backflow prevention
devices on certain residential service connections based on a
review by the Engineering Section.
The Division shall also
determine the type and location of each backflow prevention
device.
32. PLACEMENT
OF BACKFLOW
PREVENTION
DEVICE
FOR DOMESTIC
SERVICE
INSIDE
BUILDING
Backflow
prevention devices
for Domestic water lines must be installed in a vault or heated
enclosure if the distance from the curb box to the point of
entry into the building is 150 feet or more, otherwise the
Backflow
prevention
device
should be installed in the building immediately after the water
meter. The type of devise used depends on the degree of hazard
and must be approved by the Cleveland Division Water Engineering
Section. When a reduced pressure Backflow
prevention
device
is specified, the backflow may be placed in the building
regardless the distance from the curb box to the point of entry
into the building.
If a Heated Enclosure is used, it must be placed on private
property, such that the it does not restrict, limit or impact in
any way the line of site needed to safely ingress or egress the
premises. The location of the heated enclosure must be shown on
the site plan. The site plan must signed by the city, village,
district, or county engineer. Upon request, the Backflow
prevention
device
may be installed in a heated enclosure.
33. REQUIRED
HEATED ENCLOSURES FOR
Backflow
prevention
DEVICES FOR
FIRE SERVICE CONNECTIONS
Backflow
prevention device
for Fire supply lines must be installed in a vault or heated enclosure
if the distance from the curb box to the point of entry into the
building is 50 feet or more, otherwise the backflow may be
installed in the building. The type of devise used depends on
the degree of hazard and whether or not there are yard hydrants
installed on the fire supply line. The type of devise for
fire lines must be approved by the Cleveland Division Water's
Backflow Unit. When a Heated Enclosure is used, it must be
placed on private property, such that it does not restrict,
limit or impact in any way the line of site needed to safely
ingress or egress the premises. The location of the heated
enclosure must be shown on the site plan. The site plan must
signed by the city, village, district, or county engineer. Upon
request, the Backflow
prevention device
may be installed in a heated enclosure.
|